Merlin Gerin
Du er her:
 
Produkter
 Merlin Gerin
 Lavspenning
 Modulære DIN-skinneprodukter Multi 9
 Boligskap/Sikringsskap
 Underfordelingsskap og inntakskapslinger
 Effektbrytere
 Tavlesystem Prisma Plus
 Lastbrytere
 Måling, overvåking mm
 Vigilohm isolasjonsovervåking
 PowerLogic PM tavleinstrumenter
 Vigirex jordfeilreléer
 Tette, multifunksjonelle kapslinger IP65
 Industrikontakter (rundstiftmateriell)
 Mellomspenning
 LonWorks
 Telemecanique
 Sarel
 Thorsman
 Wibe
 Merten
 Norwesco
Klikk for å se undergrupper
* Ny / oppdatert

PM200 MULTIMETER

Teknisk informasjon

Tekniske dataVerdi
ProduktspekterPowerLogic PM200
kallenavn på utstyrPM200
Produkt eller komponent typepower meter
power quality analysisup to the 15th harmonic
type målingfrekvens
effektfaktor (total)
apparent power (total)
active power (total)
reactive power (total)
strøm (per phase)
voltage (per phase)
ENERGY (total)
[Us] merkespenning125...250 V DC
100...415 V AC (50/60 Hz)
network frequency50/60 Hz
power consumption in VA5 VA
Displaytypebacklit LCD
display resolution6 lines
sampling rate32 samples/cycle
measurement current5 A mA
1 A mA
analogue input typestrøm 0.01...6 A (impedance <= 0.12 Ohm)
målespenning10...480 V AC 45...65 Hz phase to phase
10...277 V AC 45...65 Hz phase to neutral
Målenøyaktighet± 0,01 Effekt
± 0.5 % strøm (1...6 A)
± 0.5 % voltage (50...227 V)
± 0.02 Hz frekvens (45...65 Hz)
nøyaktighets klasseklasse 1 (active energy according to IEC 62053-21)
electromagnetic compatibilitylimits for harmonic current emissions, conforming to IEC 61000-3-2
conducted and radiated emissions, conforming to EN 55011 klasses A
susceptibility to electromagnetic fields class class III, conforming to IEC 61000-4-3
conducted RF disturbances class class III, conforming to IEC 61000-4-6
electrostatic discharge immunity test class class III, conforming to IEC 61000-4-2
electrical fast transient/burst immunity test class class III, conforming to IEC 61000-4-4
1.2/50 µs shock waves immunity test class class III, conforming to IEC 61000-4-5
immunity to impulse waves class class III, conforming to IEC 61000-4-8
immunity to microbreaks and voltage drops class class III, conforming to IEC 61000-4-11
limitation of voltage changes, voltage fluctuations and flicker in low-voltage, conforming to IEC 61000-3-3
Monteringsmetodeinnfelt montering
mounting supportpanel
installasjonstypeindoor installation
overvoltage categoryIII
IP-gradIP30 (bakside) conforming to IEC 60529
IP52 (forside) conforming to IEC 60529
Relativ fuktighet95 % 50 °C
Forurensning type2
ambient air temperature for operation-5...55 °C
ambient air temperature for storage-40...85 °C °C
operating altitude0...3000 m m
StandarderIEC 61010-1
UL 508
CSA C22.2 No 14
ProduktsertifikaterCE
cULus
Bredde96 mm mm
Dybde69 mm
Høyde96 mm mm
Vekt0.34 kg kg

<<< Tilbake